SRB301LC-24V






| Ordering data | |
|
Replacement article number
|
101165472 |
| Product type description | SRB301LC-24V |
| Article number (order number) | 101163475 |
| EAN (European Article Number) | 4,25012E+12 |
| eCl@ss number, version 12.0 | 27-37-18-19 |
| eCl@ss number, version 11.0 | 27-37-18-19 |
| eCl@ss number, version 9.0 | 27-37-18-19 |
| ETIM number, version 7.0 | EC001449 |
| ETIM number, version 6.0 | EC001449 |
| Available until | 31.12.2024 |
| Approvals - Standards | |
|
Certificates
|
TÜV |
| cULus | |
| CCC | |
| EAC | |
| TILVA | |
| General data | |
|
Standards
|
EN IEC 62061 |
| EN ISO 13849-1 | |
| EN IEC 60947-5-1 | |
| EN IEC 60947-5-3 | |
| EN IEC 60947-5-5 | |
| EN IEC 61508 | |
| EN IEC 60204-1 | |
| EN IEC 60947-1 | |
| Climatic stress | EN 60068-2-78 |
| Enclosure material | Glass-fibre reinforced thermoplastic, ventilated |
| Material of the contacts, electrical | AgSn0. self-cleaning, positive drive |
| Gross weight | 250 g |
| General data - Features | |
|
Stop-Category
|
0 |
| Wire breakage detection | Yes |
| Cross-circuit detection | Yes |
| Start input | Yes |
| Feedback circuit | Yes |
| Automatic reset function | Yes |
| Earth connection detection | Yes |
| Integral system diagnostics, status | Yes |
| Number of auxiliary contacts | 1 |
| Number of LEDs | 4 |
| Number of normally closed (NC) | 2 |
| Number of safety contacts | 3 |
| Safety classification | |
|
Standards
|
EN IEC 60947-5-1 |
| EN IEC 61508 | |
| Safety classification - Relay outputs | |
|
Performance Level, stop 0, up to
|
e |
| Category, Stop 0 | 4 |
| Diagnostic Coverage (DC) Level, Stop 0 | ≥ 99 % |
| PFH value, Stop 0 | 2.00 x 10⁻⁸ /h |
| Safety Integrity Level (SIL), Stop 0, suitable for applications in | 3 |
| Mission time | 20 Year(s) |
| Common Cause Failure (CCF), minimum | 65 |
| Mechanical data | |
|
Mechanical life, minimum
|
10,000,000 Operations |
| Mounting | Snaps onto standard DIN rail to EN 60715 |
| Mechanical data - Connection technique | |
|
Termination
|
rigid or flexible |
| Screw terminals M20 x 1.5 | |
| Terminal designations | IEC/EN 60947-1 |
| Cable section, minimum | 0.25 mm² |
| Cable section, maximum | 2.5 mm² |
| Tightening torque of Clips | 0.6 Nm |
| Mechanical data - Dimensions | |
|
Width
|
22.5 mm |
| Height | 100 mm |
| Depth | 121 mm |
| Ambient conditions | |
|
Degree of protection of the enclosure
|
IP40 |
| Degree of protection of the mounting space | IP54 |
| Degree of protection of clips or terminals | IP20 |
| Ambient temperature, minimum | -25 °C |
| Ambient temperature, maximum | +45 °C |
| Storage and transport temperature, minimum | -40 °C |
| Storage and transport temperature, maximum | +85 °C |
| Resistance to vibrations | 10...55 Hz, Amplitude 0.35 mm, ± 15 % |
| Restistance to shock | 30 g / 11 ms |
| Ambient conditions - Insulation values | |
|
Rated impulse withstand voltage Uimp
|
4 kV |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Electrical data | |
|
Frequency range
|
50 Hz |
| 60 Hz | |
| Rated operating voltage | 24 VAC -15% / +10% |
| 24 VDC -15%/+20%, residual ripple max. 10% | |
| Rated AC voltage for controls, 50 Hz, minimum | 20.4 VAC |
| Rated control voltage at AC 50 Hz, maximum | 26.4 VAC |
| Rated AC voltage for controls, 60 Hz, minimum | 20.4 VAC |
| Rated control voltage at AC 60 Hz, maximum | 26.4 VAC |
| Rated AC voltage for controls at DC minimum | 20.4 VDC |
| Rated control voltage at DC, maximum | 28.8 VDC |
| Electrical power consumption | 1.7 W |
| Electrical power consumption | 1.9 VA |
| Contact resistance, maximum | 0.1 Ω |
| Note (Contact resistance) | in new state |
| Drop-out delay in case of power failure, typically | 80 ms |
| Drop-out delay in case of emergency, typically | 20 ms |
| Pull-in delay at automatic start, maximum, typically | 100 ms |
| Pull-in delay at RESET, typically | 20 ms |
| Electrical data - Safe relay outputs | |
|
Voltage, Utilisation category AC-15
|
230 VAC |
| Current, Utilisation category AC-15 | 6:00 SA |
| Voltage, Utilisation category DC-13 | 24 VDC |
| Current, Utilisation category DC-13 | 6:00 SA |
| Switching capacity, minimum | 10 VDC |
| Switching capacity, minimum | 10 mA |
| Switching capacity, maximum | 250 VAC |
| Switching capacity, maximum | 8:00 SA |
| Electrical data - Digital inputs | |
|
Conduction resistance, maximum
|
40 Ω |
| Electrical data - Digital Output | |
|
Voltage, Utilisation category DC-12
|
24 VDC |
| Current, Utilisation category DC-12 | 0.1 A |
| Electrical data - Relay outputs (auxiliary contacts) | |
|
Switching capacity, maximum
|
24 VDC |
| Switching capacity, maximum | 2:00 SA |